Manufacturing November 2026

Demand Charges and Peak Shaving: What Your Plant Is Really Paying For

Demand charges can be a large share of a plant's electric bill, set by a few minutes of peak draw. How billing demand is really calculated under your tariff, how to find your own peaks in interval data, and how to size a battery on power and energy before you ask for a quote.

For many manufacturers, electricity costs are about more than how much power they use. A significant part of the bill can come from how much power they draw at their busiest moment.

These are demand charges, and they are easy to miss. A plant can run efficiently all month, and one short burst of high usage can set the billing peak and raise the whole bill. Cutting total consumption does not necessarily fix it.

Other articles in this series cover why utilities charge for demand and what the return looks like. Why Your Electricity Bill Is So High — And Why Solar Fixes the Right Problem explains demand charges as an infrastructure cost-recovery mechanism, and The ROI of Solar for Manufacturers: What Most Plant Operators Don’t Realize puts a full financial model around peak shaving at a manufacturing plant. This article does something different. It is a working guide to the mechanics: how billing demand is actually set under a real tariff, why the details of your rate schedule can change the answer by tens of thousands of dollars, how to find your own peaks in interval data, and how to size a battery on two separate dimensions, power and energy, before you ask anyone for a quote.

It is written for plant managers, energy managers, and facilities leaders who want to understand their own bill well enough to judge any proposal that arrives.


Energy Charges Versus Demand Charges

Energy charges are based on total electricity consumed, measured in kilowatt-hours (kWh). Demand charges are based on the highest level of power you draw during a measurement interval, measured in kilowatts (kW). In simple terms, energy charges measure how much you use, and demand charges measure how much you need at your busiest point.

That is why using less electricity overall does not automatically lower your demand charges. A plant can reduce consumption and still pay for a costly peak. It is also why two plants with identical monthly kWh totals can have very different bills: the one with a spiky load profile pays more for demand than the one with a steady one.


How Billing Demand Is Actually Set

Most explanations stop at “the highest 15 minutes of the month.” The real tariff is more specific, and each specific feature changes what you should do. Read your rate schedule, not just your bill, and look for the following.

The Measurement Interval

Many utilities measure demand in 15-minute intervals, though rules vary by utility and rate schedule. Some use 30 or 60 minutes, and some use rolling rather than fixed windows. The key point is that demand is the average power over the interval, not an instantaneous spike.

That averaging matters. Suppose a plant runs at a steady 1,000 kW and, for three minutes during a 15-minute interval, a group of machines starts together and pushes the load to 2,000 kW. The interval average is (1,000 kW × 12 minutes + 2,000 kW × 3 minutes) ÷ 15 = 1,200 kW. That three-minute event adds 200 kW to the billing demand if it sets the peak. At $20 per kW, that is $4,000 for the month from a few minutes of operation.

The same arithmetic shows what a battery has to do. To cut that interval’s average by 200 kW, the battery must deliver 50 kWh during the interval (200 kW × 0.25 hour). It does not need to carry the whole plant, just the part of the load that pushes the interval average above your target.

Ratchets and Minimum Billing Demand

Some tariffs set billing demand as the greater of the current month’s measured peak or a percentage of the highest peak in a lookback period, often the previous eleven months. This is called a demand ratchet. The percentage varies widely by utility and rate schedule.

The effect is that a single bad peak can follow you for a year. As an illustration, suppose your July peak is 1,200 kW and your tariff has an 80 percent ratchet over eleven months, which sets a minimum billing demand of 960 kW. If your actual peaks in later months fall to 700 kW, you still pay for 960 kW, an extra 260 kW. At $20 per kW, that is $5,200 per month, or about $57,200 over the following eleven months. (These figures are illustrative, and later peaks in a real plant may not fall that far.)

Ratchets change the economics of peak shaving in two ways. First, savings from shaving can be delayed, because a high peak from last summer may keep setting your billing demand until it ages out of the lookback window. Second, reliability matters more: one missed dispatch during the single highest interval of the year can reset the ratchet. A battery that is 95 percent reliable is not 95 percent as valuable under a ratchet tariff.

Time-of-Day and Seasonal Demand Rates

Some tariffs charge separately for demand measured during an on-peak window and for demand measured at any time, and some charge higher demand rates in summer or winter months. In those cases, the peak that matters most may not be your overall highest peak. It may be your highest on-peak interval.

This changes both the diagnosis and the solution. A peak that occurs at a 6 a.m. startup may be billed at a lower rate than a smaller peak at 4 p.m., and a solar array that produces strongly in the afternoon may reduce the more expensive one. Know which window and which season carries the highest rate.

Coincident Peak Charges

In some markets, certain transmission or capacity-related charges are allocated based on your load during a handful of hours when the grid as a whole peaks, rather than your own highest interval. If your tariff or supplier contract includes such a charge, your most valuable peak-shaving moments are the grid’s peak hours, which may be few and may be announced in advance or forecast.

Power Factor

Some tariffs bill demand in kVA rather than kW, or add a penalty when your power factor falls below a threshold. Manufacturers with many motors and other inductive loads often have lower power factor. If your bill includes a power-factor adjustment, check it before concluding that your demand problem is entirely a kW problem. Capacitor banks or other correction equipment may be a cheaper fix, and depending on their capabilities, some inverters and battery systems can provide reactive power support. Ask about it in any proposal rather than assuming.

Where to Find Each Feature

Tariff FeatureWhat It MeansWhy It Matters for Peak ShavingWhere to Look
Interval lengthPeriod over which demand is averagedShort bursts are diluted; sustained loads matter mostRate schedule, metering section
RatchetMinimum billing demand tied to past peaksOne bad peak can persist for months; reliability is criticalRate schedule, billing demand definition
Time-of-day demandSeparate charge for demand in an on-peak windowTarget the on-peak peak, not necessarily the overall peakRate schedule, demand charge section
Seasonal ratesDemand rate varies by seasonSummer or winter peaks may carry most of the costRate schedule
Coincident peakCharges based on load during system peak hoursValue concentrates in a few grid-peak hoursRate schedule, supplier contract
Power factorkVA billing or penalty below a thresholdSome “demand” cost may be fixable without storageRate schedule, bill adjustments

What Actually Causes a Plant Peak

The most useful questions are not only how much you use, but when you use the most and what causes it. Common triggers include shift startups, air compressors, HVAC during extreme temperatures, production surges, and several high-load systems running at the same time.

Picture a shift change where several large machines start at once, compressors kick in, and HVAC is running hard. For a few minutes, demand jumps. Depending on the tariff, that interval can set your billing demand for the month, even if usage returns to normal right after.

Two additional patterns are worth looking for. The first is coincidence: a peak is often not caused by one big load but by several moderate loads that happen to overlap, which means a scheduling change can sometimes remove it. The second is concentration: in many plants, a small number of intervals, sometimes a fraction of one percent of the month, set the charge. That is good news, because it means the problem is narrow, and a narrow problem can often be solved with a system smaller than the plant’s total load.


Solar Alone Versus Solar Plus Storage

Solar reduces the electricity you buy, which helps with energy charges. But if your peak happens when solar output is low, such as an early startup or a cloudy afternoon, solar alone may not lower your billed demand much. A single cloud passing during the one interval that sets your peak can erase the benefit for the whole month.

Battery storage adds control. A battery can discharge when load spikes, such as when production lines start together, and reduce what you pull from the grid at that moment. This is called peak shaving. Solar generates the power, and storage manages when it is used.

One more factor is the season. In winter, evening peaks often occur after sunset, so a battery may be charged partly from the grid in off-peak hours rather than from solar, as discussed in Commercial Solar in Winter: What Snow, Clouds and Shorter Days Really Do to Your ROI. The demand-charge benefit can still be strong, but the value comes from peak management, not from free solar energy.


A Step-by-Step Method for Finding Your Peaks

You can do much of this analysis yourself, or insist that any installer shows you theirs. The method below expands the basic five steps.

Step 1: Get the Tariff and the Bill Facts

Find your billed demand in kW and your demand rate per kW on a recent bill, and record every demand component: on-peak, any-time, seasonal, and any adjustments. Then pull the rate schedule itself and note the interval length, any ratchet, any time-of-day windows, and any power-factor terms. The bill shows what you paid; the tariff explains why.

Step 2: Get Interval Data

Ask your utility for interval data, ideally at 15-minute resolution, through its customer portal, a data-sharing program, or a direct request. If you have sub-meters or a building management system, collect their data too. Sub-metering often reveals which department or process drove a given interval, which the revenue meter cannot.

Step 3: Review at Least Twelve Months, Preferably Twenty-Four

A year covers the seasons, and a second year shows what is structural and what was a one-off. Seasonal patterns matter because summer cooling and winter heating often create different peaks, and because a ratchet may carry a one-time event forward.

Step 4: Build Four Views of the Data

  1. The monthly peak list. The highest interval in each month, with date and time.
  2. The top-intervals list. The twenty or fifty highest intervals across the whole period, with timestamps.
  3. The load duration curve. All intervals sorted from highest to lowest. It shows how steeply the load rises at the top, and therefore how much shaving a small battery could deliver.
  4. The typical-day profile by season. Average load by hour for weekdays and weekends in each season.

Step 5: Attribute Each Peak

Match the peak intervals against production schedules, shift changes, maintenance logs, compressor logs, HVAC trends, and equipment startup records. Classify each peak as structural (it happens every Monday at shift start) or one-off (a maintenance restart, an equipment test, an extreme-heat day). Structural peaks are targets for scheduling, controls, or storage. One-offs may call for a process change or simply for awareness.

Step 6: Choose the Fix

Decide whether scheduling changes, equipment controls, power factor correction, solar, storage, or a combination would help. Cheaper operational fixes, such as staggering startups or sequencing compressors, often come first, and they also shrink any battery you eventually need.

An Illustrative Result

Suppose the monthly peak list for a plant looks like this:

MonthPeak (kW)MonthPeak (kW)
Jan1,080Jul1,230
Feb1,050Aug1,200
Mar1,090Sep1,120
Apr1,100Oct1,090
May1,130Nov1,060
Jun1,210Dec1,070

The question is how low to set the shaving target, and the answer depends on how much each step down costs. At an illustrative demand rate of $20 per kW per month, with no ratchet, the results for three targets are as follows.

Shaving TargetDemand Cut in Worst MonthAnnual Demand SavingsBattery Power NeededWorst-Day Energy to ShaveImplied Duration
1,100 kW130 kW$7,800About 130 kWAbout 88 kWhAbout 0.7 hours
1,050 kW180 kW$16,600About 180 kWAbout 158 kWhAbout 0.9 hours
1,000 kW230 kW$28,600About 230 kWAbout 250 kWhAbout 1.1 hours

The savings figures come from adding up, for each month, how many kilowatts the peak exceeds the target: 390, 830, and 1,430 kW-months respectively. The worst-day energy figures assume the load exceeds the target for several consecutive intervals on the worst day, with the excess tapering off, and they are for illustration only. Real interval data gives the real answer.

Notice what the table shows. Moving the target from 1,100 to 1,050 kW adds $8,800 per year in savings for about 50 kW more power and about 70 kWh more energy. Moving from 1,050 to 1,000 adds $12,000 per year for about 50 kW and about 92 kWh more. Each step adds both savings and cost, and the right stopping point is where the added savings no longer justify the added battery cost. That is a calculation you can only do with quoted prices, which is why the analysis comes before the proposal, not after.


kW and kWh: Sizing a Battery on Two Dimensions

How big does a battery need to be? It depends on power (kW), which sets how much demand it can offset, and energy (kWh), which sets how long it can do so. Interval data is essential before sizing.

Size the power rating to the deepest reduction you want. If you want to cut your worst-month peak by 180 kW, the battery must be able to discharge at least 180 kW at the moment of that peak. A battery with a lower power rating cannot achieve the reduction, however much energy it stores.

Size the energy capacity to the worst day’s excess. Add up the energy above your target across the intervals on your worst day (excess kW × 0.25 hour per interval) to see how much the battery must deliver. Then add margin for round-trip losses, degradation over time, usable capacity limits, and forecast error. A battery sized exactly to the historical worst day has no room for a slightly worse one.

Check the duration. Dividing energy by power gives the implied duration. Many peak-shaving applications land around one to two hours of storage, though plants with long, flat peaks need more and plants with brief spikes need less.

Plan for recharging. The battery must recharge between events without creating a new peak while it charges. Charging should be controlled against your demand target and, where relevant, scheduled outside any on-peak window. If consecutive-day events are possible, the system needs enough recharge time between them.

Plan for dispatch reliability. Under a ratchet, the highest interval of the year matters most. Forecast-based dispatch, alerts when the system does not respond, and a clear owner for responding to them protect the savings. The responsibility questions around alerts and response are covered in Developer, EPC, Financier, Monitoring Vendor: Who Owns the Gaps?


What the Return Looks Like

The core value is avoided demand charges. In the source example, if a battery cuts your billing demand by 100 kW and your demand rate is $20 per kW, that is $2,000 saved in that billing month. Across a year, the actual figure depends on how many months the battery reduces the peak and by how much, which is what the monthly peak list above shows.

A battery can also keep critical equipment running during certain outages, which matters when a short interruption can hit schedules, inventory, and customer commitments. That resilience dimension is covered in Solar + Storage as Insurance, Not Infrastructure. Batteries enrolled in demand response or virtual power plant programs may earn additional revenue, covered in Is Your Roof a Profit Center? The Rise of Virtual Power Plants (VPPs) in 2026.

Actual results depend on your tariff, load profile, and system design, and storage is not the right fit for every facility.


Is Your Plant a Good Candidate? A Screening View

A quick way to screen is the load factor, your average demand divided by your peak demand. A plant with a 900 kW average and a 1,230 kW peak has a load factor of about 73 percent, which in this example leaves a gap between peak and typical load that a battery could address. A plant with a very steady, around-the-clock load has a high load factor and less to shave.

Signs of a Good CandidateSigns of a Weaker Candidate
Demand charges are a large share of the billDemand charges are small or the rate per kW is low
Peaks are sharp and short, set by a small number of intervalsLoad is flat, with the peak close to the average
Peaks recur on a predictable patternPeaks are random and unpredictable
A ratchet or high on-peak rate makes each kW costlyBilling demand is set by something storage cannot influence
Cheaper operational fixes have already been triedOperational fixes could solve most of the problem
The tariff is stableA rate redesign is expected that could change the value

A note on the last row: utilities do redesign demand charges, sometimes adding time-differentiated demand or changing ratchets. Ask your installer to test the project against your current tariff and against plausible changes, and ask your utility whether alternative rate schedules are available to you.


What to Request Before You Sign Anything

From your utility:

  • The full rate schedule and any riders, with the demand charge, ratchet, interval, time-of-day, and power-factor terms identified
  • Twelve to twenty-four months of interval data, at 15-minute resolution if available
  • Your billing demand history by month
  • Any alternative rate schedules you are eligible for

From any installer proposing storage:

  • A peak-shaving simulation run on your actual interval data, not a typical-customer profile
  • The target demand level, the power (kW) and energy (kWh) ratings, and the reasoning behind each
  • How the model treats your ratchet, time-of-day windows, and seasonal rates
  • The dispatch method (threshold-based or forecast-based), how charging is controlled, and how the system behaves when solar output is low
  • What demand reduction is guaranteed, how it is measured, and what the remedy is if it falls short
  • The battery’s warranty terms, including cycle and throughput limits, and how those interact with any grid-service programs
  • Who monitors the system, who is alerted when it fails to respond, and how quickly

Frequently Asked Questions

What is a demand charge? A utility fee based on the highest power demand you record in a billing interval, measured in kW rather than kWh. The details, including the interval length, any ratchet, and any time-of-day rules, are set by your rate schedule.

Can solar alone reduce it? Sometimes, when it is producing strongly during your peak interval. It is not consistent, because clouds, early-morning startups, and evening peaks can fall outside solar production. Storage adds reliability.

How big does a battery need to be? It depends on power (kW), which sets how much demand it can offset, and energy (kWh), which sets how long it can do so. Interval data is essential before sizing, and the right target depends on the cost of each additional kilowatt and kilowatt-hour compared with the savings it adds.

How does a ratchet change the economics? It means a single high peak can set your minimum billing demand for months, so savings may be delayed and a missed dispatch can be costly. Ask whether your tariff has a ratchet and model it explicitly.

Where do I get interval data? Most utilities provide 15-minute interval data to commercial customers through an online portal or on request. Sub-meters and building management systems can add detail about which processes drive each interval.

Should we try operational changes first? Usually, yes. Staggering startups, sequencing compressors, and correcting power factor are often inexpensive and can shrink the peak. Doing them first also means any battery you buy is sized for the remaining peak, not the original one.


Peak shaving is not about using less electricity. It is about using power more strategically, and knowing exactly how your tariff measures your busiest moment is the first step to doing so. The plants that capture the most value are the ones that understand their own billing demand before they talk to a vendor.


Power Solar can review your rate schedule and interval data to identify what sets your billing demand and whether storage, solar, or operational changes would reduce it. Contact us to start with your own numbers.

The conversation

See the numbers for your facility.

In 30 minutes we'll model the OpEx you can cut, the NOI you can lift, and the payback you can expect — specific to your site, not a brochure average.

300+ MWOn-site capacity deployed
1,200+Facilities powered
$2.2B+Lifetime power savings
10 yrsIn business
Trusted by NABCEP Certified · Licensed & insured · Projects nationwide
Raising Cane's Culver's Sonic Drive-In U.S. Air Force